Thermal discharge safety device
- For protecting boilers with integrated hot water heaters on the temperature side in closed hot water heating systems in accordance with DIN EN 12828 (DIN 4751) up to max. 100 KW, which are operated with solid fuels.
- Component-tested
- For solid fuel boiler
Suitable for “thermal discharge safety device” 90 029 01, 90 843 68-69 ...
- With double sensor fuse
- For solid fuel boiler
- Permanently set to: 95°C
- The valve can be installed horizontally, vertically or in inverted position. The thermowell of the temperature sensor supplied with the valve must be installed on the supply line at a distance < 0.5 m from the heat generator or at the highest point in the boiler and in any case before the outflow line. Use of the thermowell supplied with the valve is prescribed.
- Used with a double sensor fuse as a safety device in heating systems that use a stove or fireplace as a heat generator. The device combines thermal flow protection and a filling valve in one block, which can be activated simultaneously with positive safety when controlled by a remote sensor.
Technical data: - Permanently set to: 100°C