TECO®
- Model GST for domestic installation according to DVGW-VP305, as a measure to actively deter manipulation in accordance with TRGI
Technical properties:
Horizontal installation: for metal conductors and plastic pipes
Vertical installation: only for metal conductors, flow direct from bottom upwards
Operating pressure: 15-100 mbar
Operating temperature: -20°C to +60°C
Pressure loss: dp<0.5 mbar
Overcurrent: VL <30 lt/h at 100 mbar
External temperature resistance: 925 °C - 5 bar
Internal temperature resistance: 200 °C
Area of application: all gas types according to EN437 and DVGW G260/1 - Flow direction from external to internal thread (E/I)
- Polished and chrome-plated with thermal fittings fuse
- Ball seals made of: Teflon
- Spindle seals: O-ring made of NBR 70 ShA
- External thread: DN 15 (1/2”)
- Connecting gas stoves, -cookers, -grills, -baking ovens and -heating appliances
- For all plug-in gas hoses with standard plug according to DIN 3383 Part 1
- According to EN 331 / DVGW
- For gauge counter G2.5-G6
- Operating pressure: 5 bar
- Model GST for domestic installation according to DVGW-VP305, as a measure to actively deter manipulation in accordance with TRGI
Technical properties:
Horizontal installation: for metal conductors and plastic pipes
Vertical installation: only for metal conductors, flow direct from bottom upwards
Operating pressure: 15-100 mbar
Operating temperature: -20°C to +60°C
Pressure loss: dp<0.5 mbar
Overcurrent: VL <30 lt/h at 100 mbar
External temperature resistance: 925 °C - 5 bar
Internal temperature resistance: 200 °C
Area of application: all gas types according to EN437 and DVGW G260/1
Function:
the flow monitor blocks the line when the flow rate selected is achieved. After the cause is rectified, pressure compensation occurs via an overflow opening, which enables the safety device to re-open.
Construction:
the internal springs do not come into contact with the flow of gas, which means they do not get dirty, ensuring a long service life. The overview opening is also protected in the open position to safeguard the re-opening function.
!!! Particularly low pressure loss (< 0.5 mbar) !!! - Flow direction from internal to external thread (I/E)
- DN 20 - DN 50
- With a lead seal and lockable device
- DIN-DVGW-approved
- External thread: DN 15 (1/2")
- Trigger temperature TSD: 96 °C
- Response time: approx. 20 sec.
- According to EN 331 / DVGW
- For gauge counter G2.5-G6
- Operating pressure: 5 bar
- According to EN 331 / DVGW
- For gauge counter G2.5-G6
- Operating pressure: 5 bar
- Assembly unit for connecting gas twin pipe meter DN 25 x DN 32 (1 1/4”)
- According to EN 331 / DVGW
- Operating pressure: 5 bar
- Made of brass with full passage
- Suitable for gas installations with low pressure (natural gas, mains LPG) gas, compressed air, fuels and heating oil
- Operating pressure: 0.1 to 5 bar
- Compact water meter installation section for flush-mounted installation, pre-assembled
- With spacer pipe DN 20 (3/4”), length 80 mm
- Shut-off ball valve with replaceable seal seat
- Polished and chrome-plated with thermal fittings fuse
- Ball seals made of: Teflon
- Spindle seals: O-ring made of NBR 70 ShA
- Compact water meter installation section for flush-mounted installation, completely pre-assembled
- With DN 20 (3/4") spacer pipe
- Shut-off ball valve with replaceable seal set, optionally motorisable
- Suitable for Ultra Flush-mounted valves
- Internal operating handle
- ø 75 mm
- For installations in the areas of drinking water, industry, cooling and heating (for measuring instruments with a sensor connection)
- Suitable for drinking water in accordance with UBA whitelist
- Operating pressure: 40 bar
- Suitable for Ultra Flush-mounted valves
- Internal operating handle
- ø 75 mm
- Package consisting of:
- 5x Gas flow monitors DN 25 (1"), 15-100 mbar, 4 m³/h
Free of charge: 2x leak finder 400 ml spray can
+ 1 x ice scraper 2K WS free of charge!
- IT x ET
- For installations in the areas of drinking water, industry, cooling and heating (for measuring instruments with a sensor connection)
- Suitable for drinking water in accordance with UBA whitelist
- Operating pressure: 40 bar
- Assembly unit for connecting gas twin pipe meter DN 25 x DN 32 (1 1/4”)
- According to EN 331 / DVGW
- Operating pressure: 5 bar
- K4 is a shut-off system that can be fitted in any environment without affecting the aesthetics. The compact design makes fitting easy.
- Installation box with adjustable fixing brackets
- Replaceable valve body